GST DI-M9101 Addressable Multi Detector with DB-M01 Base (UL Listed)

• Dual Detection Technology: Combines photoelectric optical smoke scatter with a 57.2°C (135°F) thermal heat sensor
• Safety Certification: Fully listed and certified under UL 268 (smoke) and UL 521 (heat) North American standards
• Programmable Sensitivity: 2 field-selectable smoke sensitivity levels (Level 1: 1.23%–2.7%/ft, Level 2: 2.0%–3.89%/ft)
• Onboard Diagnostics: Built-in microprocessor supporting self-diagnosis, chamber drift compensation, and 14-event history storage
• Visual Annunciation: 360-degree visible red LED indicator with selectable flashing polling mode and steady alarm illumination
• Remote Output Circuit: Dedicated polarized terminals to drive an external remote indicator lamp (e.g., GST C-9314P)
• Universal Base Supplied: Includes the GST DB-M01 standard ceiling base with non-polarized 2-wire SLC loop terminals

Best Price Guaranteed

Description

The GST DI-M9101 Addressable Multi Detector with DB-M01 Base is an intelligent combination life-safety sensor engineered by GST (Carrier) to provide rapid fire warning across diverse emergency scenarios.

By integrating an advanced infrared photoelectric smoke chamber with a precision semi-conductor thermal sensor, the GST DI-M9101 detects slow-smoldering combustion as well as fast-burning open flames.

Certified in strict compliance with UL 268 and UL 521 standards, the sensor provides dependable false-alarm immunity against transient dust and steam while maintaining fast response times under 20 seconds.

Technical Specifications Table

Product Model GST DI-M9101 Intelligent Combination Heat & Photoelectric Smoke Detector
Mounting Base Model GST DB-M01 Standard Common Detector Base (Included)
Brand Portfolio GST (Carrier)
Standards & Approvals UL Listed (UL 268 for Smoke Detection & UL 521 for Heat Detection); NFPA 72 Compliant
Operating Loop Voltage 24 VDC Nominal (16 VDC to 28 VDC operating range, Power Limited)
Standby Current ≤ 0.8 mA (Quiescent monitoring current)
Alarm Current ≤ 1.8 mA (Without remote indicator) / ≤ 3.8 mA (With remote indicator active)
Smoke Detection Principle Infrared light-scattering photoelectric chamber
Heat Detection Principle Semi-conductor thermal sensor (Fixed Temperature & Rate-of-Rise)
Thermal Action Temperature 57.2°C (135°F Fixed Temperature Threshold)
Smoke Sensitivity Levels Level 1: 1.23% to 2.7% per ft | Level 2: 2.0% to 3.89% per ft
Onboard Event Storage Internal MCU stores up to 14 chronological historical records
Addressing Method Electronic addressing via P-9910B Handheld Programmer (Address range: 1 to 242)
Visual Alarm Indicator Red omnidirectional LED (360° viewing; flashes on polling, steady on alarm)
Remote Output Support Polarized 2-wire output for remote indicator connection (e.g., GST C-9314P)
Wiring Constraints Non-polarized 2-core cable for SLC loop (Terminals 1 & 3); Polarized for remote LED (Terminals 2 & 4)
Enclosure Material & Color Flame-retardant ABS Plastic | Color: White (RAL 9016)
Ingress Protection Rating IP2X (Certified strictly for indoor ceiling mounting)
UL Operating Environment 0°C to +37.8°C (32°F to 100°F), ≤ 95% Relative Humidity non-condensing
Physical Dimensions Diameter: 100 mm × Height: 54.5 mm (Assembled with DB-M01 Base)
Unit Weight Approximately 110 g

⚙️ Engineering & Architecture Resources

Ensure multi-criteria sensor spacing, ceiling airflow patterns, and loop line capacitance thresholds comply with NFPA 72 standards and UL Life Safety Equipment Standards before completing final site commissioning for your GST DI-M9101 detection grid.

📥 Download Official Technical Submittal Datasheet (DI-M9101-DS)

Multi-Criteria Detection & Microprocessor Stability with GST DI-M9101

The operational core of the GST DI-M9101 combines optical scattering with rate-of-rise and fixed-temperature thermal monitoring into a single low-profile enclosure.

Standard single-technology optical sensors can experience delayed responses with fast-burning alcohol or clean chemical fires. The GST DI-M9101 eliminates detection gaps by analyzing real-time fluctuations across both smoke obscuration and ambient temperature curves simultaneously.

Long-term field stability is sustained by integrated drift compensation algorithms. As airborne dust and ambient particulate settle over time, the internal processor dynamically recalibrates its baseline reference value.

This automated compensation maintains uniform sensitivity throughout the device lifespan, preventing nuisance alarms while ensuring full sensitivity during authentic fire emergencies.

Commissioning and routine maintenance workflows are streamlined through electronic address programming and built-in diagnostic tools. Using the GST P-9910B handheld programming unit, technicians configure loop addresses from 1 to 242 and customize sensitivity settings digitally.

The detector stores up to 14 historical event records internally, allowing service technicians to review operational data directly on site during routine maintenance sweeps.

  • Dual-Sensor Multi-Criteria Logic: Combines optical light scatter with 57.2°C thermal detection to capture flaming and smoldering fires.
  • Internal 14-Event History Buffer: Stores diagnostic and alarm event data directly in the onboard MCU for fast troubleshooting.
  • Electronic Device Addressing: Eliminates mechanical switch wear and simplifies loop setup via handheld programming tools.
  • 360-Degree Visual Alarm LED: Omnidirectional light pipe ensures clear visual confirmation of system status from any ceiling angle.

Frequently Asked Questions (FAQ)

Q1: What types of fire hazards is the GST DI-M9101 multi-sensor best suited for?
A: The GST DI-M9101 is ideal for commercial offices, hotels, educational facilities, and industrial premises where both slow-smoldering materials (wood, paper, textiles) and fast-flaming thermal hazards (solvents, electrical gear, alcohol) may be present.

Q2: Does this product listing include the detector mounting base?
A: Yes. This package includes both the GST DI-M9101 addressable multi-sensor head and the matching GST DB-M01 standard ceiling base.

Q3: How is the address and sensitivity programmed on the GST DI-M9101?
A: Loop addresses (from 1 to 242) and dual smoke sensitivity levels are configured electronically using the GST P-9910B handheld digital programmer.

Q4: Can the flashing polling LED on the GST DI-M9101 be disabled?
A: Yes. In environments such as hotel guest rooms or hospital wards where blinking lights are disruptive, the polling LED can be turned off via programmer parameters while remaining fully functional to illuminate steady red during an alarm.

Q5: What are the loop wiring and remote indicator connections on the DB-M01 base?
A: Connect the 2-wire SLC loop across Terminals 1 and 3 (non-polarized). Terminals 2 (positive) and 4 (negative) provide a dedicated polarized output circuit for an external remote indicator lamp (such as the GST C-9314P).

Q6: How can technicians perform local testing on the GST DI-M9101 without test smoke?
A: The detector contains a built-in magnetic reed switch. Placing a magnetic commissioning wand near the marked test zone activates an alarm test routine to verify loop transmission and panel signaling.

Reviews

There are no reviews yet.

Be the first to review “GST DI-M9101 Addressable Multi Detector with DB-M01 Base (UL Listed)”

Your email address will not be published. Required fields are marked *

We Don't Just Sell Products, We Deliver Complete Solutions.

From planning to handover – Loop Shop is your single point MEP partner.

Expert Consultant

Get advised from our MEP Specialist

Supply & Installation

Professional installation by certified engineers

Testing & Commissioning

Ensuring system works perfectly

After Sales Support

AMC & 24/7 technical support

Have Project in Mind?

Get free and consultations and quotation for your project. 

Need Help Deciding?

Leave your number and we'll contact you with the best offer.


Notice: ob_end_flush(): Failed to send buffer of zlib output compression (0) in /home/loopshop/public_html/wp-includes/functions.php on line 5581