Description
The Simplex 49AO-WRF Addressable Sounder is a next-generation TrueAlert ES audible notification appliance engineered to provide high-integrity, addressable emergency signaling across modern life-safety networks. Controlled and supervised directly over an intelligent IDNAC Signaling Line Circuit (SLC), this advanced indoor electronic horn provides location-specific diagnostics and high-performance audio projection. Housed in a rugged, impact-resistant red thermoplastic cover featuring bold white “FIRE” markings, it delivers a loud, penetrative alarm tone that ensures immediate attention across commercial, institutional, and industrial real estate complexes.
Technical Specifications Table
| Model Assignment | 49AO-WRF (TrueAlert ES Addressable Wall Mount Electronic Horn) |
| Manufacturer Family | TrueAlert ES Addressable Peripherals by Simplex (Johnson Controls) |
| Country of Origin | Mexico |
| Loop Communication Protocol | IDNAC Signaling Line Circuit (SLC) Allocation (1 Device Address Node) |
| Channel Wiring Capacity | Maximum of 127 addresses per SLC loop | 139 maximum unit loads |
| Operating Loop Voltage | 23 VDC to 31 VDC Special Application (Regulated 29 VDC from host controller) |
| Maximum Active Current Draw | 23 mA maximum at 31 VDC nominal alarm activation |
| Supervisory Loop Current | 1 Unit Load (Equivalent to 0.8 mA maximum control panel current draw) |
| High Volume Sound Output | 92.5 dBA (Anechoic Chamber) | 89.8 dBA (UL 464 Reverberant Room) at 10 ft |
| Low Volume Sound Output | 86.7 dBA (Anechoic Chamber) | 83.4 dBA (UL 464 Reverberant Room) at 10 ft |
| Acoustic Range Frequency | 2400 to 3700 Hz frequency sweep modulated at a clear 120 Hz response rate |
| Wiring Terminal Block | Plate-mounted screw blocks supporting solid or stranded lines from 18 to 12 AWG |
| Operating Temperatures | 32°F to 122°F (0°C to 50°C) certified strictly for indoor facility environments |
| Humidity Resilience Window | 10% to 93% RH at 104°F (40°C) non-condensing moisture boundaries |
| Housing Scale Dimensions | 5-1/8″ H x 5″ W x 1-1/2″ D (130 mm x 127 mm x 38 mm) | Weight: 0.7 lbs |
| Agency List Compliance | UL 464 Listed, ULC-S525 Listed, FM Approved, CSFM Certified |
⚙️ Engineering & Architecture Resources
Verify IDNAC voltage drop margins, Class A circuit constraints, and legacy addressable panel compatibility matrices in the official technical submittal sheet: S49AO-0001.pdf.
TrueAlert ES Intelligent Operations & Automated Self-Test Diagnostic Advantages
The defining operational benefit of the Simplex 49AO-WRF Addressable Sounder is its integration with TrueAlert ES technology running on IDNAC loops. Unlike traditional notification circuits where an entire wire line must be tested manually, the 49AO-WRF features an advanced, automated Self-Test mode. Armed with internal acoustic sensors, the device tests its own horn output circuitry and reports back to the central console panel automatically.
- Dual Output Level Settings: Features switch-selectable configuration parameters to alternate between High and Low volume outputs, giving an absolute 6 dBA adjustment range to meet localized room acoustics.
- Latching Cadence Control: The horn operates completely independently from visible strobes on the same loop, responding instantly to panel commands for Temporal Code 3, March Time (60 BPM), or continuous tones.
- Rear-Zero Enclosure Footprint: The specialized clean back profile does not extend into the electrical gang box, leaving maximum workspace inside the wall box for heavy field wiring loops.
- Polarized Supervision Network: Built with a diode-polarized configuration to enforce strict loop wiring supervision, ensuring any downstream open faults are reported instantly to the control interface.
Frequently Asked Questions (FAQ)
Q1: What unique workflow benefit does the TrueAlert ES Self-Test feature offer?
A: It utilizes built-in internal sensors to physically test the sounder mechanism and report results back to the central panel, allowing for automated diagnostic sweeps without requiring manual room-by-room walkthroughs.
Q2: Can the 49AO-WRF addressable sounder be wired onto the same circuit as loop strobes?
A: Yes. Operating on an IDNet or IDNAC two-wire loop, it can share a single pair of circuit wires with visual appliances while allowing the panel to silence the horn independently while strobes remain flashing.
Q3: How do technicians physically check the assigned address code of this sounder in the field?
A: By placing a standard test magnet near the designated bottom area of the housing, the diagnostic LED will pulse out the exact binary loop address assigned to that specific unit.
Q4: Is an independent auxiliary 24V power line required to run this addressable sounder?
A: No. Operating current, system commands, and diagnostic telemetry are drawn entirely over the two-wire IDNAC circuit, which supplies a constant, regulated 29 VDC output loop.
Q5: Can the acoustic sound level be lowered for small office spaces or echoing stairwells?
A: Yes. You can toggle the output volume level from High down to Low via internal configuration switches, or install an optional 4905-9838 mechanical sound damper to drop output by an extra 5 to 6 dBA.
Q6: Which central fire alarm control panels natively drive this addressable notification appliance?
A: It integrates natively with modern addressable Simplex control units equipped with IDNAC channels, including the 4007ES, 4010ES, and 4100ES platform series.
Q7: What type of box mounting does this red wall sounder support?
A: The low-profile chassis template attaches securely to standard single-gang, double-gang, or 4-inch square electrical backboxes for easy surface or semi-flush wall installation.